Design Considerations
-
Design DX systems with 2 or 3 zones max.
- Unlimited with Chiller applications
-
All zones must have a minimum of 3.5 outlets per ton – (per zone)
-
4 ton system
- 4 x 3.5 = 14 outlets per zone minimum
- 3 zones x 14 outlets = 42 outlets total
- 42 outlets divided by 4 tons = 10 outlets/ton
-
2 zone systems can be designed with as high as 5 outlets per ton per zone (10/ton total outlets)
- Not recommended to use a bypass duct on DX coil systems
Outlets Per Zone (Per Ton)
| System Tonnage |
Minimum Outlets/Zone |
2 Zone Min w/ Max |
3 Zone Min-Max |
Total System Outlet Max |
| 2 |
7 |
7 w/ 14 |
7 |
21 |
| 2.5 |
9 |
9 w/ 18 |
9 |
27 |
| 3 |
11 |
11 w/ 22 |
11 |
33 |
| 3.5 |
12-13 |
12 w/ 24 |
12 |
36 |
| 4 |
14 |
14 w/ 28 |
14 |
42 |
| 5 |
18 |
18 w/ 36 |
18 |
54 |
Example
Zone 2 Load requires 6 Outlets
Zone 1 Load requires 15 Outlets
3 ton, 2 zone
(3 ton X 3.5 = 11 outlets/zone minimum)
Z-1 = 15 outlets (5/ton)
Z-2 = 11 outlets (3.5/ton min)
26 outlets total = 8.5 / Ton